Ventilation AI

Prästslättsvägen · exhaust fans (Bastec GP712 duct-pressure setpoint) · last plan 13 Nov 12:01
Buildings
10
planned every hour
Would trim now
9
1 held by a safety guard
Plans, last 7 days
1 680
changes made: 0
Heat it would save
782 kWh
last 7 days ≈ 424 SEK

Buildings

BuildingNowSetpointMeasuredAI would setOutdoorFlatsWould save7 daysWhy
Prästslättsvägen 2
shadow · last plan 12:01
Would trim110 Pa110 Pa105 Pa
-5 Pa
3.5 °C22.1 °C706 W104 kWhoutdoor 3.5 °C: trim 35 % of the room → 102 Pa
Prästslättsvägen 4
shadow · last plan 12:01
Would trim120 Pa120 Pa115 Pa
-5 Pa
3.1 °C22.4 °C658 W96 kWhoutdoor 3.1 °C: trim 38 % of the room → 111 Pa
Prästslättsvägen 6
shadow · last plan 12:01
Safety guard110 Pa87 Pa110 Pa
3.0 °C22.3 °C0 W0 kWhSafety guard: the fan gets 34 % but its controller asks 100 % — forced or manual in the panel; duct pressure 87 Pa vs setpoint 110 Pa
Prästslättsvägen 8
shadow · last plan 12:01
Would trim110 Pa110 Pa105 Pa
-5 Pa
2.6 °C22.1 °C726 W99 kWhoutdoor 2.6 °C: trim 42 % of the room → 101 Pa
Prästslättsvägen 12
shadow · last plan 12:01
Would trim110 Pa109 Pa105 Pa
-5 Pa
3.8 °C22.7 °C727 W9 kWhoutdoor 3.8 °C: trim 32 % of the room → 103 Pa
Prästslättsvägen 14
shadow · last plan 12:01
Would trim110 Pa109 Pa105 Pa
-5 Pa
3.5 °C22.7 °C717 W101 kWhoutdoor 3.5 °C: trim 35 % of the room → 102 Pa
Prästslättsvägen 16
shadow · last plan 12:01
Would trim130 Pa130 Pa125 Pa
-5 Pa
3.6 °C22.6 °C618 W82 kWhoutdoor 3.6 °C: trim 34 % of the room → 121 Pa
Prästslättsvägen 18
shadow · last plan 12:01
Would trim115 Pa116 Pa110 Pa
-5 Pa
2.3 °C22.8 °C731 W107 kWhoutdoor 2.3 °C: trim 44 % of the room → 105 Pa
Prästslättsvägen 22
shadow · last plan 12:01
Would trim102 Pa102 Pa97 Pa
-5 Pa
3.9 °C22.5 °C763 W95 kWhoutdoor 3.9 °C: trim 32 % of the room → 96 Pa
Prästslättsvägen 24
shadow · last plan 12:01
Would trim125 Pa124 Pa120 Pa
-5 Pa
4.0 °C22.6 °C621 W87 kWhoutdoor 4.0 °C: trim 31 % of the room → 117 Pa

Setpoint: what the exhaust-fan controller holds now. AI would set: the next step the AI plans (at most 5 Pa per hour, never more than 20 % below the building's own setpoint, never below the minimum airflow). Would save: heat not blown out at that setting, from the airflow model (airflow assumed until measured figures are in).